Uimp = 4 kV
UOC MAX = 1000 V
≤ Up = 4 kV
II
InC = 10 AThe sum of the IB must not be greater than InA.
InA = 240 A
Itotal (8/20 µs) = 40 kA
RDF = 1
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 1.5 mm² | 16 mm² | Cu |
| Type of device | Quantity | Conductor cross-section min. | Conductor cross-section max. | Connection type | Connection size | Conductor cross section | Conductor type | Conductor material | |
|---|---|---|---|---|---|---|---|---|---|
| 24 | 1.5 mm² | 16 mm² | Screw connection | solid, stranded, flexible | round | Cu | ||
| 1 | 0 mm² | 120 mm² | Bolt connection | M 10 |
Tool operation
stainless steel external brackets
IP65IP degree of protection of the included Cable glands 24x AKM 16: IP66, IP67, IP69, sealing range 5 mm - 10 mm
IP degree of protection of the included Cable glands 25x AKM 20: IP66, IP67, IP69, sealing range 6.5 mm - 13.5 mm
IP degree of protection of the included Cable glands 2x AKM 40: IP66, IP67, IP69, sealing range 19 mm - 28 mm
IK08
ready for connection
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Polycarbonate
Yes
Yes
505 mm
900 mm
170 mm
17.5 kg
transparent
DIN EN IEC 61439
20001236
4012591116127
1
85371098
DYNAMIC: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-8.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-7.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-6.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-5.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-4.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
Insulation-enclosed power distribution board as power switchgear and controlgear assembly (PSC) in accordance with IEC 61439-2 for wall mounting. The enclosures must be suitable for outdoor installation - harsh environment and/or outdoor installation - the climatic effects on the equipment must be considered. Bottom parts and lids of the boxes made from impact-resistant polycarbonate, halogen and silicone-free, colour RAL 7035, transparent lid with quick action fasteners for tool operation. Burning behaviour according to IEC 60695-2-11 glow wire test + 960°C. Maximum water absorption 10 mg in accordance with DIN 53473. Protective measure: totally insulated (protection class II), Make: HENSEL Mi Power distribution board.
PV generator connection box with string fuses, DC isolator 250 A and surge arrester, 24 x PV string to 1 x inverter input, dimensions HxWxD 475 x 900 x 170 mm